TROUBLE SHOOTING

Mounting issues

Possible cause
Connector Socket are fittet in the panel

Solution
Remove Connector Sockets with an allen key and fit the end cap or cut off end

Possible Cause
If you try to click on BOTH sides of the panel at the same time or try to force it into place using i.e. a closed fist or a hammer, the mounting brackets might break.

Solutions
Replace bracket and click panel on by open hand – one panel side at the time with low presure

Light and PSU issues

Possible cause 
Power Cord not connected to panel or PSU

Solution
Connect the Power Cord to the panel (Power In) and to the PSU

Possible cause
The Power Cord is facing the wrong way (+/- polarization)

Solution
Turn the Power Cord connector 180 degr.

 

Possible cause
No 230VAC power the PSU

Solution
Check the 230VAC connection to the PSU and make sure the circuit breaker is on

Possible cause
230VAC to the PSU is ok, but 24 VDC output missing

Solution
PSU defective. Replace.

Possible cause
Connector Sockets and/or Connector Pins are missing in an assembly or not installed correctly

Solution
Fit missing Connector Sockets and Connector Pins

Possible cause
Fault in the light panel

Solution
Replace Light Panel

Possible cause
The Power Cord is not connected correctly

Solution
Check Power Cord connection to PSU and Light Panel

Possible cause
The power cord is defective

Solution
Replace Power Cord

Possible cause
Current/voltage is adjusted too low on the back of the PSU (Type A/AB/DA only)

Solution
Adjust the PSU correctly – See guide

Possible cause
A connection between two panels is defective

Solution
Check and correct weak connection

Possible cause
PSU’s are not adjusted correctly (voltage/current)

Solution
Adjust the PSUs correctly to equal light levels – See Guide

Light Control

Possible cause
Master Sensor is not correctly configured

Solution
Needs to be reconfigured – contact LED iBond support

Possible cause
Sensor lacks voltage or is not connected correctly to the DALI bus

Solution
Check connections

Possible cause
Sensor defektive

Solution
Replace sensor

Possible cause
The Master device is not powered?

Solution
1. If Master device flash when the remote control is being used the power to the master device is OK!

2. Otherwise check the DC suppy to the master. It shall read 12 V DC between the red wire (+) and the gray wire (-) from the Zhaga socket.

Possible cause
Master device (sensor) not turned correctly into the Zhaga socket.

Solution
Check that all pins are connected

Possible cause
DALI Bus not powered

Solution
1. Check that there is ~16 V DC between the DALI wires at the Driver and that the polarity at driver is correct: Blue wire at driver is DALI+ and white wire is DALI-

2. Check that there is ~16 V DC between the DALI wires at the Master device and that the polarity at Zhaga Socket is correct: Yellow is DALI+ and Grey is DALI-

GRACY™ trouble shooting

Mounting issues

Light and PSU issues

Possible cause 
Light panel (24VDC) not connected to the PSU

Solution
Check 24 VDC power connection from light panel to the PSU

Possible cause
The 24 VDC power connection is not polarized correctly (+/- polarization)

Solution
Connect cable from light panel and PSU with correct polarization

Possible cause
No 230VAC power to the PSU

Solution
Check the 230VAC connection to the PSU and make sure the circuit breaker is on

Possible cause
230VAC to the PSU is ok, but 24 VDC output missing

Solution
PSU defective. Replace.

Possible cause
Light panel is defective

Solution
Replace light panel

Possible cause
The 24VDC power connection to the light panel  is not connected correctly

Solution
Check 24VDC power connection from light panel to the PSU

Possible cause
The PSU is defective

Solution
Replace PSU (Power Supply)

Possible cause
Current/voltage is adjusted too low on the back of the PSU (Type A/AB/DA only)

Solution
Adjust the PSU correctly – See guide

Possible cause
Panel with dimmed light is not connected correctly to the PSU or cable is defective.

Solution
Check that all light panels are properly connected to the PSU and that 24VDC cable is working properly.

Light Control

Possible cause
Master Sensor is not correctly configured

Solution
Needs to be reconfigured – contact LED iBond support

Possible cause
Sensor lacks voltage or is not connected correctly to the DALI bus

Solution
Check connections

Possible cause
Sensor defektive

Solution
Replace sensor

Possible cause
The Master device is not powered?

Solution
1. If Master device flash when the remote control is being used the power to the master device is OK!

2. Otherwise check the DC suppy to the master. It shall read 12 V DC between the red wire (+) and the gray wire (-) from the Zhaga socket.

Possible cause
Master device (sensor) not turned correctly into the Zhaga socket.

Solution
Check that all pins are connected

Possible cause
DALI Bus not powered

Solution
1. Check that there is ~16 V DC between the DALI wires at the Driver and that the polarity at driver is correct: Blue wire at driver is DALI+ and white wire is DALI-

2. Check that there is ~16 V DC between the DALI wires at the Master device and that the polarity at Zhaga Socket is correct: Yellow is DALI+ and Grey is DALI-